Hi hopefully somebody can point me in the right direction. my boiler refuses to light and just makes no attempt to do anything, I have replaced accenuator on 3 way valve as initially this seemed to cure the problem. However now I have to wait approx 30 mins-1hour with fuse switched off at wall, when i switch on it then fires up and runs for approx 1 minute before cutting off, not by little red reset and this is still in original position, it then refuses to do anything except if I turn off fuse and repeat sequence. Any help greatly appreciated.
Hi thanks for that Martyn I have removed wires from boiler to pump and hard wired this in via an extension lead. Now central heating and water working. Sorry to pester but how do I go forwards from here as cannot run extension lead all time as I assume not meant to be continuos.
Once again your help will be greatly received.
Martin
check that your pump is running, sounds to me that the heat in the boiler is not being removed, thats why after an hour it will fire again when it has cooled down